Fuses
Fuses IEC Cylindrical
Fuses IEC Cylindrical is a group of 107 IMPA-coded items (codes 794031–796156) under Fuses in the Electrical Equipment section (IMPA 79). All of them are priced per piece. The list runs through 4 metric sizes from 8×32 mm to 22×58 mm.
Buying guide
Cylindrical (ferrule) fuse links are the ceramic-bodied cartridge fuses with silver-plated end caps used in the ship’s distribution boards, starters and control panels. The group has two categories, gG/gL and aM. They come in four sizes, 8 × 32, 10 × 38, 14 × 51 and 22 × 58 mm, rated at 400, 500 or 690 V AC.[1][2]
The electrical officer holds them as spares and reorders by the marking on the fuse that blew. IMPA’s note on the group: gG/gL means full-range breaking capacity for general use, and aM means partial-range breaking capacity for motor protection.[1]
How to specify it
Give the category, size, rated voltage and rated current, exactly as marked: for example gG 14 × 51 mm 690 V 16 A. The voltage is not fixed by the size. In maker tables it drops at the top ratings. In Eaton’s 14 × 51 gG range, 1 to 25 A is 690 V, 32 and 40 A are 500 V and 50 A is 400 V. In 10 × 38, 0.5 to 25 A is 500 V and 32 A is 400 V.[3]
Do not swap categories. gG gives full-range protection for cables, motors and networks. aM interrupts currents from about 6.3 times its rating upwards. It gives short-circuit protection only and must be paired with other switchgear, such as an overload relay, for overload protection.[4][5]
The "8 × 32" size is the 8.5 × 31.5 mm fuse that some makers list as 8 × 31. It is a 400 V size with a breaking capacity of 20 kA, against 80 to 120 kA for the larger sizes. Say whether a striker (for a micro-switch fuse indicator) is needed. Eaton offers strikers in 14 × 51 and 22 × 58 only.[6][3]
Rules and certificates
IEC 60269-1 is the general standard for these fuses. It covers enclosed current-limiting fuse links with breaking capacities of at least 6 kA, for AC circuits up to 1,000 V. Fuses are made interchangeable by characteristics and dimensions, so a replacement must have the same characteristics and identical dimensions.[7][8]
On ships, IEC 60092-202 requires short-circuit protection by circuit-breakers or fuses. It permits fuses for overload protection up to 320 A, recommends breakers above 200 A, and does not accept fuses for overload protection in high-voltage AC systems. Where fuses protect polyphase motors, protection against single-phasing has to be considered.[9]
For US-flag ships, 46 CFR 111.53-1 requires each fuse to have an interrupting rating sufficient for the short-circuit current where it is fitted, and bans renewable-link cartridge fuses. COSWP says never exceed the rated capacity of wires and fuses and never use makeshift fuses. When a fuse is pulled to isolate equipment, the person working on it keeps the fuse until the job is finished.[10][11]
Questions buyers ask
- What is the difference between gG and aM fuses?
- gG is a full-range fuse that protects against both overload and short circuit, for cables and general circuits. aM is a partial-range fuse for motor circuits with high starting peaks. It covers short circuits only and needs an overload relay with it.
- Can I replace a gG fuse with an aM fuse?
- No. The circuit would lose its overload protection. Replace with the same category, size, voltage and current rating as the fuse that came out.
- Is an 8x32 fuse the same as 8x31 or 8.5x31.5?
- Yes. Mersen sells the size as 8 × 32 with dimensions 8.5 × 31.5 mm, and Eaton lists the same size as 8 × 31.
Sources
- IMPA catalogue on ShipServ: Fuses IEC Cylindrical (item notes)
- Mersen: gI-gG and aM cylindrical fuse-links, catalogue datasheet (FR8GG40V25)
- Eaton Bussmann: Technical Data 720115, Cylindrical fuse links gG/gL and aM (October 2017)
- Mersen: product page B212061, ferrule fuse-link 10x38 gG FR10GG50V1
- Mersen: NH fuse-links aM series page (partial-range breaking capacity)
- Mersen: product page Q219227, ferrule fuse-link 8x32 gG FR8GG40V2
- IEC Webstore: IEC 60269-1:2024 Low-voltage fuses, Part 1: General requirements (scope)
- IEC Webstore: IEC 60269-1:1998 (withdrawn edition), object of the standard
- IEC 60092-202:2016 Electrical installations in ships, Part 202: System design, Protection (text incorporated by reference in 46 CFR)
- US eCFR: 46 CFR 111.53-1, Fuses, general
- UK MCA: Code of Safe Working Practices for Merchant Seafarers (COSWP), 2024 edition
Published by Sherif Awad, founder of GeoMarineHub — in ship supply since 1990, a family business since 1981 (45 years). Last checked .
At a glance
Part of Electrical Equipment (IMPA section 79): Lamps, cable, switches, fuses, batteries, connectors, marine lighting fittings and meters.
It is one of 16 groups under Fuses; the others include Cartridge Fuse Bases HRC Single Pole, Cartridge Fuse Bases HRC Triple Pole, Cartridge Fuse Links HRC "0", Cartridge Fuse Links HRC "00", Cartridge Fuse Links HRC "1" and 10 more.
Post the ones you need as a requirement and verified suppliers activated at your port bid on them — sealed, so nobody sees another bid.
- Items
- 107
- IMPA codes
- 794031–796156
- Priced
- per piece
- Sizes
- 8×32 mm – 22×58 mm
Items
Also under Fuses
- Cartridge Fuse Bases HRC Single Pole
- Cartridge Fuse Bases HRC Triple Pole
- Cartridge Fuse Links HRC "0"
- Cartridge Fuse Links HRC "00"
- Cartridge Fuse Links HRC "1"
- Cartridge Fuse Links HRC "2"
- Cartridge Fuse Links HRC "3"
- Cartridge Fuses Cello-lite
- Cartridge Fuses Cello-lite UC
- D Fuse Caps
- Fuse Pullers
- Fuse Wire
Most requested sections